Power frequency test transformer
Now we have two types of test transformer:
YD-Relative humidity of HV component(Non condensing)
Voltage 5kV
~
500kV/Capacity 5kVA
~
1000kVA
YDT-Series modular type(epoxy barrel) test transformer
Voltage 10kV
~
1500kV/capacity 1.0kVA
~
1500kVA
Environment:
• Maximum Altitude 1000 m
• Altitude increases 100m, and rated voltage lowers 1%
• Operation temperature of HV component 3℃
~
+ 45℃
• Relative humidity of HV component(Non condensing) 95 %
• Operation temperature of electrical component 10℃
~
+ 45℃
• Relative humidity of electrical components (Non condensing) 80 %
• Storage and transport temperature 20℃
~
+ 60℃
• Anti-seismic 8 grade
• Grounding resistance <1.0
• No dust
Main technical parameter:
• Rated voltage:1.0kV
~
1500kV
(
and above
)
• Rated capacity: 1.0kVA
~
1500kVA
(
and above
)
• Noise
:
65dB
(
2m away from equipment
)
• PD level: 80% of rated voltage, PD2pC(or smaller as users required)
• Operation duty : at rated capacity, 1 hour on, 1hour off, 3-6 times one day; Continuously working at 50% of
rated capacity(Or other duration according to test requirement)